Design
Fixed, Demountable
or Withdrawable.
Internal Segregation
Form 4.
Rated Voltage
Up to 1000 Volts.
|
Frequency
50/60Hz.
Rated Current
3200 Amps.
(higher to special order)
|
Short Circuit Strength
Horizontal - 63kA 3 seconds.
Droppers - 50kA 1 second.
Number of Poles
3 or 4 pole.
Cable Access
Top or Bottom or Both.
|
Busbar System
The horizontal Busbar System is rated at 1200, 2400 or 3200 amps (higher ratings to special order). Neutral bars are half size (full size to special order).
Dropper bars are rated at either 500 or 630 amps (higher ratings to special order). Dropper neutral bars are full size
3 Pole or 4 Pole
The standard arrangement is 3 pole for motor starters and 3 pole plus neutral for feeders. However, the Pi2000 has been designed to accommodate a 4 pole configuration as a standard option, which makes it ideal for supplying circuits into hazardous areas such as is found in the Oil & Gas and petrochemical Industries.
|